{"id":28780,"date":"2026-11-25T17:20:00","date_gmt":"2026-11-25T22:20:00","guid":{"rendered":"https:\/\/www.autonocion.com\/us\/?p=28780"},"modified":"2026-11-25T16:15:25","modified_gmt":"2026-11-25T21:15:25","slug":"1300-megawatt-reactor-cut-off-grid-diesels","status":"publish","type":"post","link":"https:\/\/www.autonocion.com\/us\/1300-megawatt-reactor-cut-off-grid-diesels\/","title":{"rendered":"A 1,300-megawatt French reactor was cut off from the grid at 6:20 in the morning when a connection box failed on its 400,000-volt line and was shut down by hand, while a second reactor at the plant, down for maintenance, ran on emergency diesels longer than its rules allow"},"content":{"rendered":"<p>A lot has been going on at Cattenom lately.<\/p>\n<p>EDF&#8217;s news page for the four-reactor plant in northeastern France has been pretty busy since October, with a <a href=\"https:\/\/www.autonocion.com\/us\/1300-megawatt-reactor-transformer-fire-water-spray-one-of-four-on-grid\/\">transformer fire on unit 3<\/a> on October 20 and two separate updates on unit 2 later that month. So it&#8217;s easy to scroll past the short-notice EDF post about Unit 1 on Friday, November 6.<\/p>\n<p>I&#8217;d argue it&#8217;s the most interesting item on the list, though. It starts with one connection box and ends, a week later, with EDF declaring a level 1 safety event to France&#8217;s nuclear regulator.<\/p>\n<p>At 6:20 a.m. local time (12:20 a.m. on the East Coast), a fault on a 400,000-volt line cut unit 1 off from the national grid. EDF later traced it to a connection box, the housing where that high-voltage line hooks into unit 1. As power plant parts go, it&#8217;s about as unglamorous as they come, and EDF says it needs replacing.<\/p>\n<p>Unit 1 is the oldest of Cattenom&#8217;s <a href=\"https:\/\/www.edf.fr\/centrale-nucleaire-cattenom\/presentation\" target=\"_blank\" rel=\"noopener nofollow\">four pressurized water reactors, each rated at 1,300 megawatts<\/a>.<\/p>\n<h2>So what does it mean when a reactor is islanded?<\/h2>\n<p>Unit 1 didn&#8217;t just drop off the grid and go dark. EDF says it was islanded (\u00eelotage, in French), and that&#8217;s a term you probably haven&#8217;t run into unless you work around power plants.<\/p>\n<p>Basically, the reactor disconnects from the grid when the outside power goes away. Its own generator then makes only the electricity the reactor needs to stay in a safe state, keeping its pumps and systems running as a little power island.<\/p>\n<p>It&#8217;s a pretty neat trick, frankly. Unit 1 didn&#8217;t need anything from outside the fence to keep its own equipment running while the plant&#8217;s teams worked out what had broken.<\/p>\n<p>Then those teams took it offline themselves. <a href=\"https:\/\/www.edf.fr\/la-centrale-nucleaire-de-cattenom\/les-actualites-de-la-centrale-nucleaire-de-cattenom\/actualites-des-unites-de-production-ndeg1-et-3\" target=\"_blank\" rel=\"noopener nofollow\">EDF&#8217;s update on units 1 and 3<\/a>, dated November 7, said they&#8217;d shut unit 1 down on Sunday, November 8, and a later notice confirms the teams did. Neither one gives a time for the shutdown. I also can&#8217;t find a date anywhere for unit 1 going back on the grid.<\/p>\n<p>If a reactor being shut down by hand rings a bell, EDF crews did the same thing at Gravelines in late August, when they <a href=\"https:\/\/www.autonocion.com\/us\/reactors-shut-by-hand-jellyfish-four-days\/\">shut two reactors by hand before jellyfish could clog the intake screens<\/a>. Jellyfish and a bad connection box don&#8217;t have much in common. But in both cases it was the people running the plant, and not an automatic trip, that took the reactors offline.<\/p>\n<h2>Unit 3 was already down for maintenance<\/h2>\n<p>Unit 3 is where things get a bit more complicated. It shares Unit 1&#8217;s 400,000-volt line, and it was already shut down for scheduled maintenance when the fault hit. You&#8217;d probably assume a reactor that&#8217;s switched off doesn&#8217;t need much of anything from the outside world.<\/p>\n<p>So why would a reactor that isn&#8217;t running need emergency diesels?<\/p>\n<p>Because shutting a reactor down stops the chain reaction, but the fuel keeps giving off heat for a long time afterward. Pumps and safety systems have to keep moving water through the core to carry that heat away. They need electricity to do it. Normally that power comes in from outside the plant. Lose it, and the diesels take over.<\/p>\n<p>Unit 3 has two external power sources. One was already out for maintenance, and the fault on the line knocked out the other. So its emergency diesel generators started automatically, which is exactly what they&#8217;re there for, and they powered the equipment unit 3 needs to stay safe.<\/p>\n<p>EDF also says the plant has several redundant, independent power sources, and two more internal sources were still available if unit 3 needed them. So the diesels weren&#8217;t the only backup unit 3 had left.<\/p>\n<h2>EDF rated it level 1 on a scale of 7<\/h2>\n<p>The trouble was how long the diesels ran. Cattenom&#8217;s operating rulebook, which EDF calls its Technical Specifications, sets a time limit for that, and unit 3&#8217;s generators kept supplying the reactor past it. So on November 13, EDF declared a significant safety event to France&#8217;s nuclear regulator, the ASNR, at level 1 on the International Nuclear Event Scale.<\/p>\n<p>That scale runs from 0 to 7. Level 1 is the rung the international scale calls an anomaly, one step above level 0, which is for deviations with no safety significance.<\/p>\n<p>In its <a href=\"https:\/\/www.edf.fr\/la-centrale-nucleaire-de-cattenom\/les-actualites-de-la-centrale-nucleaire-de-cattenom\/indisponibilite-de-l-alimentation-electrique-externe-entrainant-le-demarrage-des-diesels-de-secours-de-l-unite-de-production-ndeg3\" target=\"_blank\" rel=\"noopener nofollow\">notice on unit 3&#8217;s diesels<\/a>, EDF says the event had &#8220;no consequence for the safety of the installations.&#8221; Basically, the rating comes from overrunning the time limit. And frankly, that&#8217;s the kind of rule you&#8217;d want a nuclear plant to be strict about.<\/p>\n<p>What EDF hasn&#8217;t published is how long the diesels actually ran, or what the limit is. I went through all three of its notices on this and couldn&#8217;t find either number, which is a little frustrating when the whole rating hinges on the gap between the two.<\/p>\n<h2>Units 2 and 4 are on a different line<\/h2>\n<p>Cattenom&#8217;s other two reactors hang off a separate 400,000-volt line, so the fault didn&#8217;t touch them. That didn&#8217;t leave the plant with much to spare, though. EDF&#8217;s <a href=\"https:\/\/www.edf.fr\/la-centrale-nucleaire-de-cattenom\/les-actualites-de-la-centrale-nucleaire-de-cattenom\/actualite-de-l-unite-de-production-ndeg1\" target=\"_blank\" rel=\"noopener nofollow\">first notice on November 6<\/a> listed units 3 and 4 as down for scheduled maintenance, which means unit 2 was the only one of the four feeding the grid that morning.<\/p>\n<p>Unit 2 kept running. Unit 4 finished maintenance and returned to the grid on November 16, according to EDF.<\/p>\n<div style=\"display: flex; flex-wrap: wrap; gap: 14px; margin: 24px 0;\">\n<div style=\"flex: 1 1 260px; min-width: 260px; background: #0f172a; color: #f1f5f9; border-radius: 14px; padding: 22px; border: 1px solid #1e293b;\">\n<div style=\"font-size: 11px; letter-spacing: 1.8px; text-transform: uppercase; color: #f87171; margin-bottom: 14px; font-weight: 600;\">Unit 1 \u00b7 1,300 MW<\/div>\n<div style=\"font-size: 30px; font-weight: 800; line-height: 1; margin-bottom: 6px;\">Islanded<\/div>\n<div style=\"font-size: 12px; color: #94a3b8; line-height: 1.4;\">Cut off from the grid at 6:20 a.m. on Nov. 6 by a failed connection box. EDF scheduled its shutdown for Nov. 8.<\/div>\n<\/div>\n<div style=\"flex: 1 1 260px; min-width: 260px; background: #0f172a; color: #f1f5f9; border-radius: 14px; padding: 22px; border: 1px solid #1e293b;\">\n<div style=\"font-size: 11px; letter-spacing: 1.8px; text-transform: uppercase; color: #f87171; margin-bottom: 14px; font-weight: 600;\">Unit 2 \u00b7 1,300 MW<\/div>\n<div style=\"font-size: 30px; font-weight: 800; line-height: 1; margin-bottom: 6px;\">On the grid<\/div>\n<div style=\"font-size: 12px; color: #94a3b8; line-height: 1.4;\">Fed by the other 400,000-volt line. The only unit supplying the grid on Nov. 6.<\/div>\n<\/div>\n<div style=\"flex: 1 1 260px; min-width: 260px; background: #0f172a; color: #f1f5f9; border-radius: 14px; padding: 22px; border: 1px solid #dc2626; position: relative;\">\n<div style=\"position: absolute; top: -10px; right: 16px; background: #dc2626; color: #fff; font-size: 10px; font-weight: bold; letter-spacing: 1.2px; padding: 4px 10px; border-radius: 20px;\">INES 1<\/div>\n<div style=\"font-size: 11px; letter-spacing: 1.8px; text-transform: uppercase; color: #f87171; margin-bottom: 14px; font-weight: 600;\">Unit 3 \u00b7 1,300 MW<\/div>\n<div style=\"font-size: 30px; font-weight: 800; line-height: 1; margin-bottom: 6px;\">On diesels<\/div>\n<div style=\"font-size: 12px; color: #94a3b8; line-height: 1.4;\">Down for maintenance on unit 1&#8217;s line. Lost its remaining external source and ran on diesels past the allowed time.<\/div>\n<\/div>\n<div style=\"flex: 1 1 260px; min-width: 260px; background: #0f172a; color: #f1f5f9; border-radius: 14px; padding: 22px; border: 1px solid #1e293b;\">\n<div style=\"font-size: 11px; letter-spacing: 1.8px; text-transform: uppercase; color: #f87171; margin-bottom: 14px; font-weight: 600;\">Unit 4 \u00b7 1,300 MW<\/div>\n<div style=\"font-size: 30px; font-weight: 800; line-height: 1; margin-bottom: 6px;\">Back Nov. 16<\/div>\n<div style=\"font-size: 12px; color: #94a3b8; line-height: 1.4;\">Fed by the other 400,000-volt line. Returned to the grid after scheduled maintenance.<\/div>\n<\/div>\n<\/div>\n<p>As of EDF&#8217;s November 16 notice, the new connection box for unit 1 was scheduled to go in within days, and unit 4 was back on the grid that same day.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>A lot has been going on at Cattenom lately. EDF&#8217;s news page for the four-reactor plant in northeastern France has &#8230; <\/p>\n<p class=\"read-more-container\"><a title=\"A 1,300-megawatt French reactor was cut off from the grid at 6:20 in the morning when a connection box failed on its 400,000-volt line and was shut down by hand, while a second reactor at the plant, down for maintenance, ran on emergency diesels longer than its rules allow\" class=\"read-more button\" href=\"https:\/\/www.autonocion.com\/us\/1300-megawatt-reactor-cut-off-grid-diesels\/#more-28780\" aria-label=\"Read more about A 1,300-megawatt French reactor was cut off from the grid at 6:20 in the morning when a connection box failed on its 400,000-volt line and was shut down by hand, while a second reactor at the plant, down for maintenance, ran on emergency diesels longer than its rules allow\">Read more<\/a><\/p>\n","protected":false},"author":8,"featured_media":28779,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[116],"tags":[],"class_list":["post-28780","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-energy","resize-featured-image"],"acf":[],"_links":{"self":[{"href":"https:\/\/www.autonocion.com\/us\/wp-json\/wp\/v2\/posts\/28780","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.autonocion.com\/us\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.autonocion.com\/us\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.autonocion.com\/us\/wp-json\/wp\/v2\/users\/8"}],"replies":[{"embeddable":true,"href":"https:\/\/www.autonocion.com\/us\/wp-json\/wp\/v2\/comments?post=28780"}],"version-history":[{"count":3,"href":"https:\/\/www.autonocion.com\/us\/wp-json\/wp\/v2\/posts\/28780\/revisions"}],"predecessor-version":[{"id":28790,"href":"https:\/\/www.autonocion.com\/us\/wp-json\/wp\/v2\/posts\/28780\/revisions\/28790"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.autonocion.com\/us\/wp-json\/wp\/v2\/media\/28779"}],"wp:attachment":[{"href":"https:\/\/www.autonocion.com\/us\/wp-json\/wp\/v2\/media?parent=28780"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.autonocion.com\/us\/wp-json\/wp\/v2\/categories?post=28780"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.autonocion.com\/us\/wp-json\/wp\/v2\/tags?post=28780"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}